VARIABLE SPEED CONTROLLER (VSC)

Markets: Residential (6VSG Only)

The VSC firmware (application program) is factory loaded and used for field upgrades or replacements.

SiteTech or OnCue software is required to upgrade the controller firmware.

Click here to download Firmware

DO NOT LOAD ON VSC.4 CONTROLLERS

Notice: If replacing controller, please transfer parameter profile to new the unit when possible.
Otherwise you must include the following parameter change: Voltage Regulator Gain = 128
This parameter can only be changed with SiteTech, it cannot be corrected with OnCue or through the controller user interface.

Version 1.3.0 July 14, 2015
Update: Support for V3(Blue board) hardware
This software is compatible only with VSG V1(Green Board) and VSG V3(Blue Board) hardware. It’s NOT compatible with V2(Red Board), RDC2 and APM units.

Version 1.02.06
Update: OnCue Plus: Remote monitoring support for OnCue Plus. OnCue will only work with USB.

Version 1.02.05
Update: Added support for the communications kit which also required change to the outputs on the PIM.
Cabinet intrusion alarm is now on output #5. Reserve Oil Empty on output #6. Change max engine speed to 3100 RPM.

Version 1.01.4
Update: Fix display not working. Fix issues with metering: voltage regulator.

Version 1.00.5
Original Release